# DG set insertion loss calculator (Inside and outside the enclosure) in dB(A) | NovaLIMS

> Free DG set insertion loss calculator by the inside and outside the enclosure method (CPCB DG set norms). Enter your readings to get insertion loss in dB(A), with the formula, a worked example and typo checks.

Source: https://novalims.in/tools/calculators/dg-insertion-loss

## How DG set insertion loss is calculated

Free DG set insertion loss calculator (inside and outside the enclosure method), following CPCB DG set norms. Enter 2 readings to get insertion loss in dB(A), with the formula filled in step by step.

1.  ### Insertion loss · dB(A)
    
    `IL = L_in − L_out`
    

## What you need

| Symbol | Reading | Unit | Notes |
| --- | --- | --- | --- |
| L_in | Average level inside the room (1 m from the DG set) | dB(A) | usually 40–140 dB(A) |
| L_out | Average level outside the room | dB(A) | usually 20–140 dB(A) |

## Worked example

Readings:

-   Average level inside the room (1 m from the DG set): **L\_in = 96.4 dB(A)**
-   Average level outside the room: **L\_out = 68.9 dB(A)**

1.  ### Insertion loss
    
    `IL = 96.4 − 68.9 = 27.5 dB(A)`
    

Result: Insertion loss **27.5 dB(A)**.

## Checks and units

-   **Typical values:** DG set enclosures: at least 25 dB(A)
-   The level outside is higher than inside: check the readings.

## Questions

### How do you calculate DG set insertion loss by the inside and outside the enclosure method?

Insertion loss = L\_in − L\_out. Here L\_in is the average level inside the room (1 m from the DG set) (dB(A)), L\_out is the average level outside the room (dB(A)). The result is in dB(A).

### What unit is DG set insertion loss reported in?

Insertion loss is reported in dB(A), to 1 decimal place.

### Which standard does this DG set insertion loss calculation follow?

It follows the calculation in CPCB DG set norms. Check it against the current edition of the standard and your lab’s SOP before reporting.

### Can you show a worked example?

With average level inside the room (1 m from the DG set) = 96.4 dB(A), average level outside the room = 68.9 dB(A), the result is insertion loss = 27.5 dB(A).

### What is a typical DG set insertion loss value?

DG set enclosures: at least 25 dB(A)

### What mistakes should I look out for?

The level outside is higher than inside: check the readings.

### Is this DG set insertion loss calculator free?

Yes. It’s free with no sign-up. The calculation runs in your browser and nothing you type is sent to NovaLIMS.

## Related calculators

-   [Day-night noise level (Ldn) (Calculation): Noise](https://novalims.in/tools/calculators/noise-ldn)
-   [Equivalent noise level (Leq) (Energy average of readings): Noise](https://novalims.in/tools/calculators/noise-leq)

[All noise & illumination calculators →](https://novalims.in/tools/calculators/noise-light)

Last reviewed 10 November 2026. Version 1. Follows CPCB DG set norms. [How we check our formulas](https://novalims.in/tools/calculators/methodology)

Check results against your own method and SOP before reporting. Found an error? [Tell us](mailto:hello@novalims.in?subject=Calculator%20check) and we’ll check it.

## Run every calculation inside your LIMS

NovaLIMS puts these calculators right beside each sample’s parameters, for every analyst in the lab.

[Book a Demo](https://novalims.in/contact) [Start Free Trial](https://novalims.in/contact?intent=trial)