# Total chlorine calculator (DPD titrimetric) in mg/L | NovaLIMS

> Free total chlorine calculator by the DPD titrimetric method (IS 3025 (Part 26)). Enter your readings to get total chlorine as Cl₂ in mg/L, with the formula, a worked example and typo checks.

Source: https://novalims.in/tools/calculators/total-chlorine

## How total chlorine is calculated

Free total chlorine calculator (DPD titrimetric method), following IS 3025 (Part 26), ISO 7393-1. Enter 4 readings to get total chlorine as Cl₂ in mg/L, with the formula filled in step by step.

1.  ### Total chlorine · mmol/L
    
    `c = c₃ × (V₄ − V₅) / V₀`
    
2.  ### Total chlorine as Cl₂ · mg/L
    
    `Cl₂ = c × 70.91`
    

## What you need

| Symbol | Reading | Unit | Notes |
| --- | --- | --- | --- |
| V₀ | Volume of test sample | ml | usually 10–200 ml |
| c₃ | Concentration of the FAS solution, as Cl₂ | mmol/L | usually 0.1–5 mmol/L |
| V₄ | FAS solution used in the titration | ml | usually 0–50 ml (a 50 ml burette) |
| V₅ | FAS solution used for oxidised manganese (0 if none) | ml | usually 0–5 ml |

### Fixed values in the formula

| Symbol | Constant | Value |
| --- | --- | --- |
| 70.91 | Molar mass of Cl₂ | 70.91 g/mol |

## Worked example

Readings:

-   Volume of test sample: **V₀ = 100 ml**
-   Concentration of the FAS solution, as Cl₂: **c₃ = 0.5 mmol/L**
-   FAS solution used in the titration: **V₄ = 4.2 ml**
-   FAS solution used for oxidised manganese (0 if none): **V₅ = 0 ml**

1.  ### Total chlorine
    
    `c = 0.5 × (4.2 − 0) / 100 = 0.0210 mmol/L`
    
2.  ### Total chlorine as Cl₂
    
    `Cl₂ = 0.0210 × 70.91 = 1.49 mg/L`
    

Result: Total chlorine as Cl₂ **1.49 mg/L**.

## Checks and units

-   The manganese correction (V₅) can't be more than the titration (V₄).
-   **Other units:** ppm (1 mg/L ≈ 1 ppm in dilute water).

## Questions

### How do you calculate total chlorine by the DPD titrimetric method?

Work through 2 steps in order. Total chlorine: c = c₃ × (V₄ − V₅) / V₀. Total chlorine as Cl₂: Cl₂ = c × 70.91. Here V₀ is the volume of test sample (ml), c₃ is the concentration of the FAS solution, as Cl₂ (mmol/L), V₄ is the FAS solution used in the titration (ml), V₅ is the FAS solution used for oxidised manganese (0 if none) (ml). The result is in mg/L.

### What unit is total chlorine reported in?

Total chlorine as Cl₂ is reported in mg/L, to 2 decimal places. The calculator can also show it in ppm (1 mg/L ≈ 1 ppm in dilute water).

### Which standard does this total chlorine calculation follow?

It follows the calculation in IS 3025 (Part 26), ISO 7393-1. Check it against the current edition of the standard and your lab’s SOP before reporting.

### Can you show a worked example?

With volume of test sample = 100 ml, concentration of the FAS solution, as Cl₂ = 0.5 mmol/L, FAS solution used in the titration = 4.2 ml, FAS solution used for oxidised manganese (0 if none) = 0 ml, the result is total chlorine as Cl₂ = 1.49 mg/L.

### What mistakes should I look out for?

The manganese correction (V₅) can't be more than the titration (V₄).

### Is this total chlorine calculator free?

Yes. It’s free with no sign-up. The calculation runs in your browser and nothing you type is sent to NovaLIMS.

## Related calculators

-   [Bromate (Ion chromatography): Chlorine & disinfection](https://novalims.in/tools/calculators/bromate)
-   [Chloramines (DPD colorimetric): Chlorine & disinfection](https://novalims.in/tools/calculators/chloramines)
-   [Residual free chlorine (Iodometric): Chlorine & disinfection](https://novalims.in/tools/calculators/residual-free-chlorine)

[All water & waste water calculators →](https://novalims.in/tools/calculators/water)

Last reviewed 10 November 2026. Version 1. Follows IS 3025 (Part 26), ISO 7393-1. [How we check our formulas](https://novalims.in/tools/calculators/methodology)